Volvo Penta Industrial Power Generation Systems in California
For commercial and municipal facilities, dependable backup and prime power are non-negotiable. Leddy Power delivers fully integrated industrial generator solutions—including Volvo Penta diesel packages and ASCO controls—for California businesses, schools, and farms. The installation teams here at Leddy Power are trained to provide a fully comprehensive service that includes selecting the proper engine for your needs and meeting compliance requirements, so that your power source is up to NFPA 110 emergency standards and California’s emission regulations.
Get a Custom Generator QuotePower Types: Standby vs Prime vs Continuous
This configuration is designed for facilities connected to the utility grid, with backup from our generator in the case of an emergency where the grid is cut off.
When you don’t have access to a power grid, we will select a generator package that will reliably serve as your primary power. This is ideal for more remote sites.
Runs unlimited hours to supply critical loads without utility support (rare in grid-connected facilities).
Sizing depends on the application. A hospital emergency switchgear might require 100% standby capacity per NFPA 110, while a remote manufacturing plant might use a prime-rated generator as the main power source. Leddy Power advises on the correct configuration for your use case.
Equipment & Compliance
Manual transfer equipment is appropriate when:
We at Leddy Power supply a myriad of brands from Volvo Penta to HIPOWER and more, appropriate for ~50kW small buildings all the way up to multi-MW systems for largescale projects.
All diesel engines are Tier 4 Final compliant for NOx/PM, meeting California CARB and SCAQMD/BAAQMD rules. For cleaner sites, we also offer natural gas units.
All of our generators are certified to UL 2200. For related ATS, we adhere to UL 1008 and UL 891/1558 for all switchgear. We also ensure compliance with NFPA 110/NFPA 99 for all systems deemed critically essential.
Weatherproof enclosures reduce noise below local ordinance limits. We consider proximity to neighbors (especially in dense LA/Orange County areas).
Automatic transfer switches, paralleling controls, and remote monitoring are included. We can also integrate generators into building management systems for automated notifications.
California Considerations
PSPS PreparednessIn high fire-risk zones (Napa, Santa Barbara, etc.), backup generators sized for resiliency are key. Leddy Power designs systems to power critical loads (e.g., water pumps, schools) during outages.
RegulationsCalifornia requires emissions permits for large diesels. We guide you through District approvals or help you opt for natural gas to avoid diesel restrictions.
Seismic RequirementsAll generator pads and enclosures are anchored to meet California seismic criteria.
Whether you need a single 250kW standby generator or a bank of units for an industrial plant, we tailor the solution to site conditions and codes.
Installation Process
Our engineers assess your electrical load profile, utility service, and space.
We choose engine/generator sets (e.g. Volvo Penta 13L diesels) and enclosures to match the calculated load plus reserves.
We are experts in complying with California's electrical, environmental, and structural permitting laws.
All of our teams at Leddy Power are certified for technical installation and are ready to set up your generator, ATS, fuel system, and electrical interdependencies. If you’re using temporary rental backup generators, we can install quick-connect panels as well.
Each system is run through a full load bank test for NFPA compliance, and we will ensure your staff is trained to operate the system safely.
- Full-Service Expert Installation
- Genuine FPT Industrial Power Generation
- Preventative Maintenance Programs
- 2-Year/ 2,000-Hr Standby Warranty
- 24/7 Emergency Service Support
FAQ
The cost of a commercial system can range from $20,000 to $200,000+, depending on power rating, enclosure, and options. Our quotes are comprehensive and account for the unit itself, installation, and commissioning.
With proper maintenance, 20+ years. Key factors are usage hours and service frequency.
The strictest US emissions standard for diesels, requiring advanced exhaust after-treatment (diesel particulate filters and SCR). All new California generators must meet this.
Yes. To comply with NFPA 110, weekly exercises and annual load bank tests are required by the state. We are happy to create this schedule and document everything for your records.
The permits most often required are electrical and structural, and air quality permits come into play for diesel engines. We will gladly assist with all of the necessary filings.